GRAVITY SANITARY SEWER NOTES: 1. THE CONTRACTOR IS TO FIELD VERIFY THE LOCATIONS, THE INVERT ELEVATIONS AND THE MATERIALS OF ALL EXISTING SEWER PIPES OR MANHOLES AT THE POINTS OF TIE-IN PRIOR TO COMMENCING ANY NEW SEWER CONSTRUCTION. SHOULD ANY LOCATION, ELEVATION OR MATERIAL DIFFER FROM THAT SHOWN ON THESE PLANS, THE CONTRACTOR IS TO CONTACT THE ENGINEER FOR DIRECTION. 2. ALL 4 INCH THROUGH 15 INCH PVC (POLYVINYL CHLORIDE) PLASTIC SEWER PIPE AND FITTINGS SHALL BE IN CONFORMANCE WITH MAG STANDARD SPECIFICATION 745 AND SHALL BE INSTALLED PER THESE PLANS, MAG STANDARD SPECIFICATIONS 601, 602 & 615 AND THE PIPE MANUFACTURER'S RECOMMENDATIONS. 3. ALL 8 INCH THROUGH 120 INCH HDPE (HIGH DENSITY POLYETHYLENE) PLASTIC SEWER PIPE AND FITTINGS SHALL BE IN CONFORMANCE WITH MAG STANDARD SPECIFICATION 738 AND SHALL BE INSTALLED PER THESE PLANS, MAG STANDARD SPECIFICATIONS 601, 602, 603 & 615 AND THE PIPE MANUFACTURER'S RECOMMENDATIONS. 4. ALL 4 INCH THROUGH 24 INCH VCP (VITRIFIED CLAY PIPE) SEWER PIPE AND FITTINGS SHALL BE IN CONFORMANCE WITH MAG STANDARD SPECIFICATION 743 AND SHALL BE INSTALLED PER THESE PLANS, MAG STANDARD SPECIFICATIONS 601, 602 & 615 AND THE PIPE MANUFACTURER'S RECOMMENDATIONS. 5. ALL 4 INCH THROUGH 24 INCH DUCTILE IRON SEWER PIPE AND FITTINGS SHALL BE ANSI THICKNESS CLASS 50 WITH AN APPROVED POLYURETHANE OR CERAMIC EPOXY INTERIOR LINING, WITH AN APPROVED PETROLEUM ASPHALTIC EXTERIOR COATING, AND SHALL BE ENCASED WITHIN AN APPROVED POLYETHYLENE ENCASEMENT. PIPES AND FITTINGS SHALL BE INSTALLED PER THESE PLANS, MAG STANDARD SPECIFICATIONS 601, 602 & 615 AND THE PIPE MANUFACTURER'S RECOMMENDATIONS. 6. ALL MANHOLE BASES, RISERS, GRADE RINGS AND TOPS SHALL BE PRECAST REINFORCED CONCRETE IN CONFORMANCE WITH ASTM C478 (LATEST REVISION), THESE PLANS, AND MAG STANDARD DETAIL 420 ARE TO BE COATED WITH APPROVED WATERP ROOF CORRISION RESISTANT SEALANT. MANHOLE BASES AND BENCHES MAY BE CAST IN PLACE. APPROVED WATERSTOPS ARE TO BE PROVIDED AT ALL JOINTS. THE INTERIOR CONCRETE RISER WALLS AND TOPS (100%) ARE TO BE COATED WITH AN INSECTICIDAL PAINT PRIOR TO FINAL ACCEPTANCE. MANHOLE ACCESS FRAMES AND COVERS SHALL BE CAST IRON IN CONFORMANCE WITH MAG STANDARD SPECIFICATION 787 AND MAG STANDARD DETAILS 423 AND 424. LETTERING ON COVERS IS TO READ "SANITARY SEWER". MANHOLE INSTALLATION SHALL BE IN ACCORDANCE WITH THESE PLANS AND MAG STANDARD SPECIFICATIONS 601 & 625. 7. UNLESS CALLED FOR OTHERWISE IN THESE PLANS, ALL SEWER SERVICE LATERALS SHALL BE CONNECTED TO THE SEWER MAIN BY INSTALLING 45 DEGREE WYE FITTINGS. SEWER TAPS AND SADDLES WILL REQUIRE WRITTEN APPROVAL FROM THE SEWER UTILITY PRIOR TO USE. FOR DEEP SEWER MAINS, THE WYE AND 1/8 BEND SHALL BE ROTATED TOWARD THE VERTICAL POSITION AS NEEDED IN ORDER TO OBTAIN 5 FEET TO 6 FEET OF COVER FROM FINISH GRADE AT THE RIGHT-OF- WAY OR AT THE TERMINUS END OF THE SERVICE LATERAL. 8. UNLESS CALLED FOR OTHERWISE IN THESE PLANS, ALL SEWER SERVICE LATERALS ARE TO HAVE 5 FEET TO 6 FEET OF COVER FROM FINISH GRADE AT THE RIGHT-OF-WAY LINE OR AT THE TERMINUS END OF THE SERVICE LATERAL. LOTS WITHOUT UTILITY EASEMENTS ADJACENT TO THE STREET RIGHT-OF-WAY SHALL HAVE THEIR SERVICE LATERALS TERMINATE JUST OUTSIDE OF THE RIGHT-OF-WAY. LOTS WITH UTILITY EASEMENTS ADJACENT TO THE STREET RIGHT-OF-WAY SHALL HAVE THEIR SERVICE LATERALS EXTENDED THROUGH THE UTILITY EASEMENT BEFORE TERMINATION.THE CONTRACTOR IS TO PLUG AND PROVIDE A LOCATOR WIRE AND STAKE AT THE TERMINUS END OF EACH SERVICE LATERAL. THE CONTRACTOR IS TO TIE/MEASURE (AND MAINTAIN RECORDS OF THE TIES/ MEASUREMENTS) THE TERMINUS END LOCATION OF EACH SERVICE LATERAL TO TWO OR MORE PROPERTY CORNERS. FAILURE OF THE CONTRACTOR TO MAINTAIN RECORDS OF SERVICE LATERALS’ TERMINUS END LOCATIONS MAY BE CAUSE TO HAVE THE CONTRACTOR TO FIELD EXPOSE SERVICE LATERALS’ TERMINUS END LOCATIONS AT NO ADDITIONAL COST TO THE CONTRACTING PARTY. WHERE CURBS ARE PROPOSED, THE CONTRACTOR IS TO MARK THE TOP OF THE CURB WITH THE LETTER 'S' ABOVE EACH SERVICE LATERAL. 9. RESIDENTIAL SEWER SERVICE LATERALS ARE TO BE 4 INCH SDR 35 PVC PIPES. COMMERCIAL SEWER SERVICE LATERALS ARE TO BE 6 INCH SDR 35 PVC PIPES. 10. THE CONSTRUCTION INSPECTOR IS ANY AGENT OF THE CONTRACTING PARTY THAT HAS BEEN RETAINED TO ASSURE THAT THE WORK COVERED BY THESE PLANS IS PERFORMED CORRECTLY AND COMPLIES WITH THESE PLANS AND ANY APPLICABLE SPECIFICATIONS. 11. IN THE PRESENCE OF THE CONSTRUCTION INSPECTOR, THE CONTRACTOR SHALL PERFORM FIVE PERCENT MANDREL DEFLECTION TESTS IN ACCORDANCE WITH ARIZONA ADMINISTRATION CODE R18-9-E301(D)(2)(I) (AND MAINTAIN RECORDS OF THE RESULTS) ON THE TOTAL LENGTH (100 %) OF ALL PVC AND/OR HDPE SEWER LINES INSTALLED. ANY SEGMENT OF PIPE FAILING THE 5 PERCENT MANDREL DEFLECTION TEST SHALL BE CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACTING PARTY. 12. IN THE PRESENCE OF THE CONSTRUCTION INSPECTOR, THE CONTRACTOR SHALL PERFORM LEAKAGE TESTS IN ACCORDANCE WITH THE ARIZONA ADMINISTRATION CODE R18-9-E301 (D)(2)(j) (AND MAINTAIN RECORDS OF THE RESULTS) ON 100% OF ALL SEWER LINES INSTALLED. THE CONTRACTOR SHALL USE THE FOLLOWING APPLICABLE TEST METHOD. 13. IN THE PRESENCE OF THE CONSTRUCTION INSPECTOR, THE CONTRACTOR SHALL PERFORM GRADE TESTS IN ACCORDANCE WITH THE ARIZONA ADMINISTRATION CODE R18-9-E301(D)(2)(K) (AND MAINTAIN RECORDS OF THE RESULTS) ON THE TOTAL LENGTH 100% OF ALL THE SEWER LINE INSTALLED FOR UNIFORM SLOPE ( BY LAMP LIGHTING, REMOTE CAMERA OR SIMILAR METHOD APPROVED BY THE UTILITY). ANY SEWER LINE THAT HAS BEEN INSTALLED AT A GRADE DIFFERENT FROM THAT CALLED FOR IN THESE PLANS, AND IS DETERMINED TO BE UNACCEPTABLE TO THE CONSTRUCTION INSPECTOR, SHALL BE RE-LAID TO THE CORRECT GRADE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACTING PARTY. 14. IN THE PRESENCE OF THE CONSTRUCTION INSPECTOR, THE CONTRACTOR SHALL PERFORM LEAKAGE TESTS IN ACCORDANCE WITH THE ARIZONA ADMINISTRATION CODE R18-9-E301 (D)(3)(F) (AND MAINTAIN RECORDS OF THE RESULTS) ON ALL COMPLETED MANHOLES FOLLOWING APPLICABLE TEST PROTOCOLS: ANY MANHOLE THAT FAILS THE LEAKAGE TEST BE CORRECTED AS DEEMED NECESSARY BY THE CONSTRUCTION INSPECTOR AT NO ADDITIONAL COST TO THE CONTRACTING PARTY. 15. STATIONING IS ALONG THE CENTERLINE OF STREETS, UNLESS NOTED OTHERWISE. 16. PER ADEQ REQUIREMENTS, A MINIMUM COVER OF 36 INCHES SHALL BE MAINTAINED OVER ALL SEWER PIPES, AS MEASURED TO FINISH GRADE, UNLESS DUCTILE IRON PIPE IS USED. 17. ALL GRAVITY SEWER PIPE SHALL BE INSTALLED STARTING AT THE LOWEST DOWNSTREAM POINT AND THEN PIPE IS TO BE LAID AS INSTALLATION PROGRESSES UPSTREAM. THE BELL END FOR EACH LENGTH OF PIPE SHALL BE AT THE UPSTREAM END AND THE SPIGOT END SHALL BE AT THE DOWNSTREAM END. 18. ALL SEWER SERVICES SHALL BE LAID TO THE CENTER OF THE LOT TO BE SERVED UNLESS NOTED OTHERWISE IN THE PLANS. 19. ANY LOT, WHICH HAS A FINISH FLOOR ELEVATION LOWER THAN THE UPSTREAM MANHOLE/CLEAN OUT RIM ELEVATION, AS DETERMINED FROM THE SEWER SERVICE CONNECTION POINT, IS TO HAVE AN APPROVED BACKFLOW PREVENTER INSTALLED ON THAT LOT'S SEWER SERVICE LINE AT THE POINT OF TERMINATION. 20. SEWER JOINT DEFLECTION SHALL NOT EXCEED PIPE MANUFACTURER’S RECOMMENDATION. PIPES SHALL NOT BE DEFLECTED AT JOINTS UNLESS CALLED FOR IN THESE PLANS. 21. WHEN APPLICABLE, THE CONTRACTOR IS TO MARK THE TOP OF CURB WITH AN "S” AT ALL SERVICE LOCATIONS AFTER CURBS ARE INSTALLED. 22. THE INLET AND OUTLET PIPE CONNECTIONS TO MANHOLES SHALL BE MADE BY THE USE OF FLEXIBLE COMPRESSION JOINTS NO CLOSER THAN 12 INCHES TO, AND NOT FARTHER THAN 36 INCHES FROM, THE MANHOLE WALL. NO FLEXIBLE COMPRESSION JOINTS SHALL BE EMBEDDED IN THE MANHOLE BASE OR BENCH.